o 2 Year warranty
o Accuracy 1% full scale
o Inputs type K, J, R and PT100

o Outputs Relay250 Vac / 5 Amps, SSR, 4-20mA
o Proportional band 2.5% full scale
o Alarms ± 5% full scale around set point

Model ANC-202 ANC-301 ANC-302 ANC-601 ANC-605 ANC-607 T-602
Dimensions 96mmx96mm 96x48mm
Input K,J,Pt100 K,J,Pt100 K,J,P,R K,J,Pt100 K,J,Pt100 K,J,P,R K,J,Pt100,R
Temperature
Range
0-100°C
0-200°C
0-400°C
0-800°C/K,J
0-100°C
0-200°C
0-400°C
0-100°C
0-200°C
0-400°C
0-800°C/K,J
0-1200°C/K
0-1600°C/R
0-99,9°C
0-199°C
0-399°C
0-100°C
0-200°C
0-400°C
0-800°C/K,J
± 50°C/Pt100
0-99,9°C
0-199°C
0-399°C
0-799°C/K,J
0-1200°C/K
0-1600°C/R
0-100°C
0-200°C
0-400°C
0-600°C/K,J
0-800°C
0-1000°C/K
0-1200°C
0-1600°C/R
Control On/Off,P,PD none
Output Relay(250V/5A), SSR(24V DC) none
Option none Output: DC 1-5V Input:
DC 1-5V
Output: DC 4-20mA Input:
DC0-5V
Hi/Low Alarm Input:
DC4-20mA
  4 digits Input:
DC0-20mA

Model ANC-272 ANC-371 ANC-671 ANC-675 ANC-677 ANC-651 ANC-657
Dimensions 72mmx72mm
Input K,J,Pt100 K,J,Pt100 K,J,Pt100 K,J,Pt100 K,J,Pt100 K,J,Pt100 K,J,Pt100
Temperature
Range
0-50°C
0-100°C
0-200°C
0-400°C
0-800°C/K,J
0-100°C
0-200°C
0-400°C
0-99,9°C
0-199°C
0-399°C
0-799°C/K,J
0-999°C/K
± 50°C/Pt100
0-100°C
0-200°C
0-400°C
0-800°C/K,J
0-99,9°C
0-199°C
0-399°C
0-799°C/K,J
0-999°C/K
0-99,9°C
0-199°C
0-399°C
0-799°C/K,J
0-999°C/K
0-99,9°C
0-199°C
0-399°C
0-799°C/K,J
0-999°C/K
Control On/Off,P,PD
Output Relay(250V/5A), SSR(24V DC)
Option none none Output: DC 1-5V   DC 1-5V
Output: DC 4-20mA DC 4-20mA DC 4-20mA
Hi/Low Alarm Hi/Low Alarm Hi/Low Alarm Hi/Low Alarm

Features:
o Easy to use:
..Neither the auto tune process nor the manual reset potentiometer adjustment is necessary
..in VD series low cost temperature controllers.
o The set point is only parameter need to be set by simply pressing the up/down key.
..Its very easy for first-time users to operate.
o High functionality at low cost:
..The VD series offer the benefits of microprocessor technology at a very competitive price.
o Built in timer funtion:
..With the built in timer, the external timer is not necessary. Saving cost.
o Alarm selection:
..PV high/low, Deviation high/low alarm modes are available.
o 4~20mA process value retransmission.
Specifications
Input Thermocouple: L, J, K, R type
RTD: PT-100 ohms
Linear: 4~20mA; 0~50mV; 0~5V; 0~10V...
Accuracy T/C ±1°C; RTD ±0.2°C
Sampling Time 2 times/second
Control P Control : Proportional Band 5%
On/Off Control:Hysresis ±2 degree
Cycle Time Relay: 15sec
Current Output SSR 1 sec.
Continuos Current(Voltage) 0 sec
Output Relay Contact Output: 10A/240 VAC(Resistive load)
Pulsed Voltage Output to Drive SSR; 0/24V(Resistive 250 ohms min)
Current Output: 4~20mA(Resistive 250 ohms max)
Continuos Voltage Output: 0~1V; 0~5V
General Rated Voltage; AC 90~264V 50/60HZ
Ambient Temperature: 0~50°C
Ambient Humidity: 0~90%
Consumption: Less than 3VA
Alarm Modes PV High Alarm
PV Low Alarm
Deviation High Alarm
Deviation Low Alarm
Soak On Timer
Soak Off Timer
Type Code 30Temperature Range
Linear L -1999°C
~9999°C
-1999°C
~9999°C
J J1 0°C~100°C 32°F~212°F
J2 0°C~200°C 32°F~392°F
J3 0°C~400°C 32°F~752°F
J4 0°C~600°C 32°F~1112°F
J5 0°C~800°C 32°F~1472°F
J6 0°C~1000°C 32°F~1832°F
K K1 0°C~200°C 32°F~392°F
K2 0°C~400°C 32°F~752°F
K3 0°C~600°C 32°F~1112°F
K4 0°C~800°C 32°F~1472°F
K5 0°C~1000°C 32°F~1832°F
K6 0°C~1200°C 32°F~2192°F
R R1 0°C~600°C 32°F~1472°F
R2 0°C~800°C 32°F~1832°F
R3 0°C~1000°C 32°F~2192°F
R4 0°C~1600°C 32°F~2912°F
T T1 -199°C~400°C -199°F~752°F
T2 0°C~100°C 32°F~212°F
T3 0°C~200°C 32°F~392°F
T4 0°C~400°C 32°F~752°F
PT100 D1 -199°C~400°C -199°F~752°F
D2 0°C~100°C 32°F~212°F
D3 0°C~200°C 32°F~392°F
D4 0°C~400°C 32°F~752°F

Features:
o Dual 4-digit LED displays(PV/SV).
o Universal Power Supply: 90-264V AC, 50/60Hz (Also available 18/32V AC/DC)
o 8 alarm modes-user selectable
o Countdown timer for setting delay of alarm relay activation.
o Ramp to setpoint and soak functions
o T/C, RTD, Linear Input configurable.
Specifications
Input Thermocouple: J,K,T,E,B,R,S,N type
RTD:DIN PT-100: JIS PT100
Linear: 4~20mA:0~50mV:0~1V:0~5V:0~10V
Accuracy T/C±1°C: PT100±0.2°C
Sampling
Time
2 times/second
Control Proportional Band:0.0~100.0%
Rest (Integral) : 0~3600 sec.
Derivative Time : 0~3600 sec.
Hysteresis (Dead Band) : 0.0~25.5%
Cycle Time : 0~100 sec
Output Relay Contact Output :5A/250 VAC
Pulsed Voltage Output to Drive SSR:
0/24V (Resistive 250 ohms/min)
Current Output : 4~20mA; 0-20mA
(Resistive 600 ohms/max)
Continuous Voltage Output : 5V; 0~10V (Resistive 600 ohms/max)
General Rated Voltage: AC 90~264V 50/60HZ
Ambient Temperature: 0~50°C
Ambient Humidity: 0~90%
Consumption: Less than 5VA
Input
Type Temperature Range
J -50°C~1000°C -58°F~1830°F
K -50°C~1370°C -58°F~2498°F
B 0°C~1800°C 32°F~3272°F
R 0°C~1750°C 32°F~3182°F
S 0°C~1750°C 32°F~3182°F
T -270°C~400°C -454°F~752°F
E -50°C~750°C -58°F~1380°F
N -50°C~1300°C -58°F~2372°F
DPT -200°C~500°C -328°F~932°F
JPT -200°C~500°C -328°F~932°F
Line -1999~9999 -1999~9999

Alarm Modes
PV High Alarm PV Low Alarm
Deviation High Deviation Low
Event-Off Timer Event-On Timer
Soak on Timer Soak on Timer

Features:
o 6 alarm modes with standby and latch function
o User menu configurable
o Various output modules
o Auto/Manual "Bumpless" transfer
o RS-485 communication
o T/C, RTD, Linear input configurable
o User friendly menu with operator lockout
o Universal power supply 90-264V AC, 50/60Hz (Also available 18/32V AC/DC)
o Fuzzy enhanced PID with Auto Tune
o 4-20mA remote setpoint input
o Process value or set point input 4-20mA retransmission
o Software filter
Specifications
Input Thermocouple: J,K,T,E,B,R,S,N,C type
RTD:DIN PT-100: JIS PT100
Linear: 4~20mA:0~50mV:0~1V:0~5V:0~10V
Accuracy T/C±1°C: RTD±0.2°C; linear ±3mV
Sampling
Time
2 times/second
Control Proportional Band:0.0~300.0%
integral Time : 0~3600 sec.
Derivative Time : 0~900 sec.
Hysteresis:0.0-200.0 or 0-2000
Cycle Time : 0~100 sec
Output Relay Contact Output :10A/240 VAC
(Resistive load)
Pulsed Voltage Output to Drive SSR:
0/24V (Resistive 250 ohms/min)
Current Output : 4~20mA; 0-20mA
(Resistive 600 ohms/max)
Continuous Voltage Output :
0-1V;0~5V;0~10V
(Resistive 600 ohms/max)
General Rated Voltage: AC 90~264V 50/60HZ
Ambient Temperature: 0~50°C
Ambient Humidity: 0~90%
Consumption: Less than 5VA
Input
Type Temperature Range
J -50°C~1000°C -58°F~1830°F
K -50°C~1300°C -58°F~2498°F
B 0°C~1800°C 32°F~3272°F
R -50°C~1750°C -58°F~3182°F
S -50°C~1750°C -58°F~3182°F
T -270°C~400°C -454°F~752°F
E -50°C~1000°C -58°F~1832°F
N -50°C~1300°C -58°F~2372°F
C -50°C~1800°C -58°F~3272°F
DPT -199°C~850°C -328°F~1562°F
JPT -199°C~600°C -328°F~1112°F
Line -1999~9999 -1999~9999

Alarm Modes
Process High Alarm Process Low Alarm
Deviation High Alarm Deviation Low Alarm
Band High Alarm Band Low Alarm


Features:
o Two 8-segment (Ramp & Soak)programmable profiles
o User menu configurable
o External run/stop selection
o Auto/Manual "Bumpless" transfer
o RS-485 or master-slave communication mode available
o T/C, RTD, Linear input configurable
Specifications
Input Thermocouple: J,K,T,E,B,R,S,N,C type
RTD:DIN PT-100: JIS PT100
Linear: 4~20mA:0~50mV:0~1V:0~5V:0~10V
Accuracy T/C±1°C: RTD±0.2°C
Sampling
Time
2 times/second
Control Proportional Band:0.0~300.0%
integral Time : 0~3600 sec.
Derivative Time : 0~900 sec.
Hysteresis:0.0-200.0 or 0-2000
Cycle Time : 0~100 sec
Output Relay Contact Output :10A/240 VAC
(Resistive load)
Pulsed Voltage Output to Drive SSR:
0/24V (Resistive 250 ohms/min)
Current Output : 4~20mA; 0-20mA
(Resistive 600 ohms/max)
Continuous Voltage Output :
0-1V;0~5V;0~10V
(Resistive 600 ohms/max)
General Rated Voltage: AC 90~264V 50/60HZ
Ambient Temperature: 0~50°C
Ambient Humidity: 0~90%
Consumption: Less than 5VA
Input
Type Temperature Range
J -50°C~1000°C -58°F~1830°F
K -50°C~1300°C -58°F~2498°F
B 0°C~1800°C 32°F~3272°F
R -50°C~1750°C -58°F~3182°F
S -50°C~1750°C -58°F~3182°F
T -270°C~400°C -454°F~752°F
E -50°C~1000°C -58°F~1832°F
N -50°C~1300°C -58°F~2372°F
C -50°C~1800°C -58°F~3272°F
DPT -199°C~850°C -328°F~1562°F
JPT -199°C~600°C -328°F~1112°F
Line -1999~9999 -1999~9999

Alarm Modes
Process High Alarm Process Low Alarm
Deviation High Alarm Deviation Low Alarm
Band High Alarm Band Low Alarm